TSIFlow Hood8380measures the air volume flowing through various air outlets ( diffusers, shutters, etc.). It is lightweight, weighing only 3.4Kg, and is easy to carry and use. Place the flow hood on the air outlet and read the air intake or exhaust volume directly on the digital display. 8380 can also work alone, or support a variety of thermal anemometer probes to provide a variety of measurement functions, and provide data storage and processing functions ( data points up to 26,500 sampling points, with time stamp).
+ Ergonomic design and ultra-light weight make it easier for personal operation
+ Detachable digital wind pressure gauge Optional Pitot tube, airflow probe, temperature probe, velocity matrix and relative humidity probe Multiple thermal wind speed probes (960 series) can be used in other applications
+ Back pressure compensation function
+ K factor function can flexibly measure the air flow through different diffusers
+ Provides a kit for biological safety cover (BSC hood)
+ A variety of hood sizes are available to facilitate users to measure the air flow of various air outlets
+ Backlit display, easy to read measurement data in the dark
+ Compact packaging, easy to transport
+ Convenient on-site calibration
+ NIST calibration certificate
+ Anti-vortex X-type flow adjustment plug-in (standard ), suitable for vortex type tuyere
+ Optional Chinese interface
Model | 8380 |
Air volume | |
Range | 42-4250m3/hr |
Accuracy | ±3% of reading or ±12m3/hr (air volume >85 m3/hr) |
Resolution | 1m3/hr |
Wind speed | |
Range | (Pitot tube) 0.125-40m/s |
Range | (Airflow probe) 0.125-25m/s |
Range | (Velocity matrix) 0.125-12.5m/s |
Accuracy | ±3% of reading or ±0.04m/s |
Resolution | 0.01m/s |
Pressure | |
Pressure difference | ±3735Pa (maximum 37.5kPa) |
Absolute pressure |
Absolute pressure 356-1016 mmHg |
Accuracy | ±2% of reading or ±0.25Pa |
Relative humidity | |
Range | 0-95%RH |
Accuracy | ±3%RH |
Resolution | 0.1%RH |
Temperature | |
Sensor | Sensor |
Temperature probe | -40-121℃ |
Temperature and humidity probe | -10-60℃ |
Resolution | 0.1℃ |
Accuracy | ±0.3℃ |
NiMH battery | 12 hours (typical) |
Interface | RS232 output |
Operating temperature | 0-60℃ |
Air volume hood size | |
Standard | 610x610 mm |
Alternative | 610x1220mm |
Alternative | 305x1220mm |
Alternative | 305x1525mm |
Alternative | 915x915mm |
Alternative | 406x406mm |
Weight | 3.4kg (when using 610x610mm air volume hood) |