Basic knowledge of clean room pressure measurement
- 2019-06-19
- 635
- Esky Purify
Features and Benefits (5815/5825):
Can use Pitot tube to measure duct velocity
Various pressure units: H2O/Pa/hPa/kPa/mmHg

Additional functions of model 5825:
Calculate air volume
Can store up to 12,700 data and 100 data groups
Includes a set of LogDat2 data download software
Test purpose: To ensure that the pressure difference of all systems and rooms in the factory meets the design requirements.
Test conditions: ① All air conditioning systems, exhaust systems and all process exhausts have been operated as required; ② All valves on the air ducts and process exhaust have been checked and ensured to be all open or can be effectively controlled; ③ The automatic control system has been debugged and put into use; ④ The exhaust fan unit has been tested for total system air volume and has met the requirements; ⑤ The air volume balance of the air outlets in each room of the system has been completed and meets the design requirements; ⑥ Ensure that the medium-efficiency filter installed on the exhaust port is within the final resistance range;
⑦ Ensure that all rooms are well sealed, the sweeping strips on the doors have been installed as required, and all perforations and other holes have been sealed;
⑧ The documents required for the test have been fully prepared.
Test method: Close the room door and use a micro-differential pressure gauge to measure the pressure difference between the room door and the adjacent room. According to the "Pharmaceutical Industry Cleanroom Design Code" (GB50457-2008), the pressure difference between clean rooms of different grades and between clean areas and non-clean areas should not be less than 5Pa; the pressure difference between the clean area and the outdoors should not be less than 10Pa.